Heat Pump and EV Charger on a 100A Panel
A heat pump and an EV charger can sometimes share a 100A panel, but big auxiliary heat strips or an unmanaged 48A charger can push the calculation over.
⚠️ Safety first: Work inside a panel or on a 240V circuit should be done by a licensed electrician, with a permit where your area requires one. This page explains the planning, not how to do the wiring.
How the optional calculation works
NEC 220.82 adds the general loads (3 VA per square foot, small-appliance and laundry circuits, and the nameplate of fixed appliances), takes the first 10 kVA at 100% and the remainder at 40%, then adds heating and cooling loads. A 100A service at 240V is 24,000 VA. The heating and cooling part is taken separately, so electric resistance strip heat can swamp the result. Check article 220.82(C) for exactly which heating and cooling loads are added, and how the EV charger is counted (nameplate or the 220.57 value) in your jurisdiction.
Example
Illustrative example only, using the NEC 220.82 method as we understand it. Real homes differ, and your electrician or inspector decides what is accepted. This is not safety clearance.
| Scenario | General loads (VA) | After 10 kVA + 40% (VA) | Plus heating/cooling (VA) | Result |
|---|---|---|---|---|
| EV 32A (7,680 VA), heat pump 4,000 VA | 27,880 | 17,152 | 21,152 | Under 24,000 VA |
| EV 48A (11,520 VA), heat pump 4,000 VA | 31,720 | 18,688 | 22,688 | Under 24,000 VA |
| EV 24A (5,760 VA), heat pump 4,000 VA | 25,960 | 16,384 | 20,384 | Under 24,000 VA |
| EV 32A, heat pump plus 10 kW strips (14,000 VA) | 27,880 | 17,152 | 31,152 | Over 24,000 VA |
Base home in this example: 2,000 sq ft with an electric range (8,000 VA), gas water heating, and a dishwasher and disposal. The heat pump figure of 4,000 VA is an assumption; use your equipment's nameplate. The pattern is the point: the margin is thin, a larger charger setting uses most of it, and big strip heat is the bigger problem.
Fixes that are commonly used
- Choose a heat pump with no strip heat or a small strip kit, and check how the heat strips are counted.
- Set the EV charger to a lower current. NEC 625.42(B) requires restricted access and a durable label showing the adjusted rating.
- Use an energy management system (NEC 625.42(A) and 750.30); see our smart load management guide.
- Use measured demand under NEC 220.87 if you have a year of data.
For the heat pump side, see heat pump electrical requirements.
Sources
Frequently Asked Questions
Q: Can a 100A panel run a heat pump and an EV charger?
A: Sometimes. It depends on the full load calculation. A smaller charger setting, no or small strip heat, or load management makes it more likely to work.
Q: Why do heat strips matter so much?
A: Resistance strip heat can add many kVA to the heating load in the NEC 220.82 calculation, often more than the EV charger.
Q: Does this example clear my panel?
A: No. It is illustrative arithmetic. Your electrician or inspector must complete the calculation for your home.