ChargePoint Home Flex on a 100-Amp Panel: Settings and Breakers
The ChargePoint Home Flex can be set from 16A to 50A, and each setting needs a matching breaker. On a 100A panel, the lower settings are the ones most likely to fit without a service upgrade.
⚠️ Safety first: Work inside a panel or on a 240V circuit should be done by a licensed electrician, with a permit where your area requires one. This page explains the planning, not how to do the wiring.
Settings and breaker sizes
ChargePoint says the Home Flex can be set to 16A, 24A, 32A, 40A, 48A or 50A. Its installation FAQ describes 32A and 40A as the most popular settings and notes that 48A and 50A may need an electrical panel upgrade. Because EV charging is a continuous load, the circuit breaker is sized at 125% of the charging current (NEC 625.41), which is why the table below pairs each setting with the next standard breaker.
| Charging current | Power at 240V | Breaker at 125% (calculated) | Installation type |
|---|---|---|---|
| 16A | 3.8 kW | 20A | Hardwired |
| 24A | 5.8 kW | 30A | Hardwired |
| 32A | 7.7 kW | 40A | Plug-in (NEMA 6-50 or 14-50) or hardwired |
| 40A | 9.6 kW | 50A | Plug-in or hardwired |
| 48A | 11.5 kW | 60A | Hardwired |
| 50A | 12 kW | 62.5A, so 70A | Hardwired |
ChargePoint states that hardwired installations accept breakers from 20A to 80A, and that plug-in installations work only with the 40A or 50A breakers that match the 32A and 40A settings. The 50A setting is listed with 70A or 80A breakers.
How the setting is changed
ChargePoint says a licensed electrician sets the amperage during installation, over Wi-Fi or over Bluetooth if Wi-Fi is not available, starting from a 16A default. After installation, the charging rate can be adjusted in the ChargePoint app up to 80% of the breaker rating or the charger's maximum output. For code purposes, NEC 625.42(B) treats an adjustable setting as acceptable only where access to the adjusting means is restricted, and the adjusted rating has to be shown on the label. Ask your electrician and inspector how they want a lowered setting recorded.
Plug-in or hardwired?
A plug-in installation uses a NEMA 6-50 or 14-50 outlet and supports only the 32A and 40A settings. ChargePoint recommends hardwiring for outdoor installs, where local code requires GFCI protection, or where no matching 240V outlet exists. It also says a GFCI breaker can be used but advises against one in general, because the Home Flex already has built-in charge-circuit protection and a GFCI breaker can cause nuisance trips. If your area requires GFCI protection on a plug-in outlet, hardwiring avoids the problem.
What this means on a 100A panel
On a 100A service, the setting you choose is a load calculation decision. A lower setting such as 24A on a 30A breaker adds less to the calculation than 40A on a 50A breaker. ChargePoint's installation page does not describe panel-level load management for the Home Flex, and says each station needs its own dedicated circuit, so you cannot share a dryer circuit with it. If a lower setting is too slow for you, see our guides to smart load management and EV chargers on 100A panels, and to the 80% rule for where the 125% factor comes from.
Sources
Frequently Asked Questions
Q: What breaker does a 40A ChargePoint Home Flex setting need?
A: A 50A breaker, because EV charging is a continuous load sized at 125%. ChargePoint lists 50A breakers for the 40A setting in plug-in or hardwired installations.
Q: Can the Home Flex be plugged in at any amperage?
A: No. ChargePoint says plug-in installation supports only the 32A and 40A settings. Higher settings must be hardwired.
Q: Who sets the Home Flex amperage?
A: ChargePoint says a licensed electrician sets it during installation, and it can then be adjusted in the app up to 80% of the breaker rating or the charger maximum.